  • 8 field selectable sequences
  • 4 or 8-point monitoring
  • Free Custom Message Labels (Order Here)
  • All common ISA sequences
  • Multiple-unit first-out indication
  • 2 SPDT relays for alarm activated devices
  • Silence, acknowledge, and reset functions
  • SafeTouch® through-glass button programming
  • Flanges for wall or pipe mounting
  • Worldwide Explosion-Proof Approvals
  • NTEP Weights & Measures Batch Controller
  • Pulse Input
RM7,025

Usually ships in 2 to 4 weeks

  • Worldwide Explosion-Proof Approvals
  • NTEP Weights & Measures Batch Controller
  • Pulse Input
RM7,540

Usually ships in 2 to 4 weeks

  • Worldwide Explosion-Proof Approvals
  • NTEP Weights & Measures Batch Controller
  • Pulse Input
RM7,540

Usually ships in 2 to 4 weeks

  • Worldwide Explosion-Proof Approvals
  • NTEP Weights & Measures Batch Controller
  • Pulse Input
RM8,054

Usually ships in 2 to 4 weeks

Description

The ProtEX-MAX PD8-150 offers all the functionality of the Vigilante II PD150 as a fully FM, CSA, ATEX, and IECEx approved explosion-proof product. It provides alarming and monitoring capabilities for all of your level, pressure, flow, and other process switches. These explosion-proof alarm annunciators are available in two models; the PD8-154 has four (4) inputs and the PD8-158 has eight (8) inputs. Each model accepts inputs from relays, float switches, digital outputs, and many other discrete (on/off) devices. They can be field programmed for all common ISA alarm sequences including first out indication and provide alarm signaling through front panel LEDs and a built in audible horn. Additional audible devices may be triggered through the use of relays. The silence, acknowledge, and reset functions can be operated without opening the housing by using the built-in SafeTouch® through-glass buttons. Custom printed message labels can be included with your order at no additional charge by completing this form.

General

Display: PD8-154: Four red LED channel indicators. PD8-158: Eight red LED channel indicators. One green LED power indicator.
Alarm Messages: Custom printed adhesive clear labels.
Area: PD154, 1.25″ x .60″ (32 mm x 15 mm), 4 messages PD158, 1.25″ x .25″ (32 mm x 6 mm), 8 messages
User specified size and length, up to 4 lines (PD154) or 2 lines (PD158) of 14 characters of size 9 pt fonts.
Programming Methods: Rear 4-position switch for sequence selection and horn operation. Three SafeTouch through-glass buttons for NO/NC input selection, sequence option, and operation when cover is installed. Three internal pushbuttons when cover is removed.
Audible Alarm: 85 dB internal horn. The use of an external explosion-proof horn is recommended due to the internal horn’s audibility being dampened by the explosion-proof enclosure.
Noise Filter: 40 ms debounce on inputs and external push buttons.
Shared First-Out Systems: 1 ms unit-to-unit delay. Maximum of 200 units in the shared first-out system.
Non-Volatile Memory: All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
Power Options: 85-265 VAC, 50/60 Hz; 90-265 VDC, 20 W max; or 12-36 VDC, 12-24 VAC, 6 W max.
Fuse: Required external fuse: UL Recognized, 5 A max, slow blow. Up to 6 annunciators may share one 5 A fuse
Isolated Power Supply: 24 VDC ± 10% @ 200 mA max Standard on 85-265 VAC powered units only.
Isolation: 4 kV input/output-to-power line.
Overvoltage Category: Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
Environmental: T6 Class operating temperature range Ta = -40 to 60°C
T5 Class operating temperature range Ta = -40 to 65°C
Connections: Removable screw terminal blocks accept 12 to 22 AWG wire.
Enclosure: Explosion-proof die cast aluminum with glass window, corrosion resistant epoxy coating, color: blue. NEMA 4X, 7, & 9, IP68. Default conduit connections: Four ¾” NPT threaded conduit openings and two ¾” NPT metal conduit plugs with 12 mm hex key fitting installed. Additional conduit opening configurations may be available; verify quantity and sizes on specific device labeling during installation.
Mounting: Four slotted flanges for wall mounting or NPS 1½” to 2½” or DN 40 to 65 mm pipe mounting.
Overall Dimensions: 6.42″ x 7.97″ x 8.47″ (W x H x D) (163 mm x 202 mm x 215 mm)
Weight: 16.0 lbs (7.26 kg)
Warranty: 3 years parts & labor

Inputs

Input Types: NO or NC switches: No external excitation required.
Open collector transistor: Open circuit voltage approx. 3.3 VDC.
Logic Levels: LOW = 0 to 0.9 VDC, HIGH = 2.4 to 28 VDC
Update Rate: 41 ms following alarm state; 1 ms for alarm state clear.
Sequences: Input follower, ISA Sequences A, F1A, F2A, F3A, M, F1M, and F3M per ISA Standard ISA-18.1-1979 R2004.
Sequence Options: A, F1A, F2A, F3A, M, F1M, F2M, and input follower with selectable options -1 (silence push button), -4 (no lock-in), and -6 (no horn) per ISA Standard ISA-18.1-1979 R2004

Relays

Rating: 2 SPDT (Form C); rated 3 A @ 30 VDC or 3A @ 250 VAC resistive load; 1/14 HP @ 125/250 VAC for inductive loads.
Electrical Noise Suppression: A suppressor (snubber) should be connected to each relay contact switching inductive loads to prevent disruption to the microprocessor’s operation. Recommended suppressor value: 0.01 µF/470 Ω, 250 VAC (PDX6901).
Relay Operation: Relay 1: Alarm state until alarm is acknowledged. Relay 2: Alarm state if any channel indicating alarm condition.
Fail-Safe Operation: Programmable independent for each relay.
Note: In fail-safe mode, relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.

Product Ratings and Approvals

FM Enclosure: Type 4X; IP66 
   Class I, Division 1, Groups B, C, D 
   Class II, Division 1, Groups E, F, G 
   Class III, Division 1, T5/T6 
   Class I, Zone 1, AEx d, IIC Gb T5/T6 
   Zone 21, AEx tb IIIC T90°C; Ta -40°C to +65°C 
   T6 Ta = -40°C to +60°C; T5 Ta = -40°C to +65°C 
   Certificate Number: 3047283 
CSA: Class I, Division 1, Groups B, C, D 
   Class II, Division 1, Groups E, F, G 
   Class III, Division 1 
   Class I Zone 1 Ex d IIC 
   Zone 21 Ex tb IIIC T90°C 
   -40°C < Tamb. < +60° C; Temperature Code T6 
   -40°C < Tamb. < +65° C; Temperature Code T5 
   Enclosure Type 4X & IP66 
   Certificate Number: 2531731 
ATEX: II 2 G D    Ex d IIC T* Gb
   Ex tb IIIC T90°C Db IP68
   Ta = -40°C to +*°C
   *T6 = -40°C to +60°C
   *T5 = -40°C to +65°C
   Certificate number: Sira 12ATEX1182
IECEx: Ex d IIC T* Gb
   Ex tb IIIC T90°C Db IP68
   Ta = -40°C to +*°C
   *T6 = -40°C to +60°C
   *T5 = -40°C to +65°C
   Certificate Number: IECEx SIR 12.0073

Applications

Level Monitoring with Level Switches

The PD8-154 ProtEX-MAX 4-Point Annuciator is ideal for tank level switch monitoring.

  • Up to 8 Individually Labeled Level Switch Inputs
  • 24 VDC Level Switch Power Supply
  • Relays for External Horns and Light Alarms
  • Easy NEMA 4X Mounting Enclosures
  • Sunlight Readable Indication

PD8-154 Level Switch

Temp Monitoring with PD8-765 and PD8-7000 Explosion-Proof Meters

Connect the PD8-765 and PD8-7000 ProtEX-MAX alarm relays to the PD8-154 ProtEX-MAX 4-Point Annuciator for temperature alarm monitoring.

  • First-Out Indication for Heating/Cooling Systems
  • Multiple Unit First-Out Indication
  • Remote Silence, Acknowledge and Reset
  • Internal Audible Horn
  • Fail-Safe Relays for Critical Applications

PD8-154 temp monitoring

Connections

PD8-154-158 wiring connections

Data Sheet: LDS8-158 Datasheets

Instruction Manual: LIM8-158_0 Instruction Manuals

Quick Start Manual: